CVE-2025-3498 – Radiflow iSAP Smart Collector Unauthenticated Remote Command Execution and Configuration Modification

The following table lists the changes that have been made to the
CVE-2025-3498 vulnerability over time.

Vulnerability history details can be useful for understanding the evolution
of a vulnerability, and for identifying the most recent changes that may
impact the vulnerability’s severity, exploitability, or other characteristics.

  • New CVE Received
    by a6d3dc9e-0591-4a13-bce7-0f5b31ff6158

    Jul. 09, 2025

    Action Type Old Value New Value
    Added Description An unauthenticated user with management network access can get and
    modify the Radiflow iSAP Smart Collector (CentOS 7 – VSAP 1.20)
    configuration. The device has two web servers that expose unauthenticated REST APIs on the management network (TCP
    ports 8084 and 8086). An attacker can use these APIs to get access to all system settings, modify the configuration
    and execute some commands (e.g., system reboot).
    Added CVSS V3.1 AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:L
    Added CWE CWE-306
    Added Reference https://www.cvcn.gov.it/cvcn/cve/CVE-2025-3498
Share the Post: